A measurement system with dual Modbus connections linked through MQTT/TLS to a remote
server: internal details and first operation results
Esp.Ing. Marcelo Castello
†1
, Esp.Ing. Rafael B. Oliva
∗2
†
Observatorio de Energ
´
ıa y Sustentabilidad (OES), UTN FRRO
Zeballos 1341 - Rosario - Santa Fe (Argentina)
1
mcastello@frro.utn.edu.ar
∗
Area Energ
´
ıas Alternativas / Instituto de Tecnolog
´
ıa Aplicada - UNPA y L&R Ingenier
´
ıa
Avda Gregores y Lero Rivera - R
´
ıo Gallegos - Santa Cruz (Argentina)
2
roliva@uarg.unpa.edu.ar
Resumen—Este trabajo presenta un sistema de medici
´
on
para equipamiento de energ
´
ıas renovables que incorpora
dos conexiones basadas en el protocolo abierto Modbus
(RTU/Serial hacia m
´
odulos internos, TCP hacia el exterior)
y logra la vinculaci
´
on entre el m
´
odulo datalogger y un
dashboard centralizado remoto. La instalaci
´
on y puesta
en marcha reciente de instrumentos de alta calidad hacen
posible reunir informaci
´
on confiable y a la vez contar
con un monitoreo y persistencia remota de los datos. El
conjunto toma informaci
´
on de viento utilizando sensores
Thies instalados en la misma torre de un aerogenerador e
informaci
´
on de corriente y tensi
´
on producida por un conjunto
de paneles fotovoltaicos y aerogenerador que cargan un banco
de bater
´
ıas y suministra energ
´
ıa a un invernadero. A su
vez, se construy
´
o y program
´
o un m
´
odulo auxiliar externo
para medici
´
on de temperatura y humedad en el invernadero,
comunicado por RS485 y protocolo Modbus RTU con el
datalogger principal. El datalogger env
´
ıa los datos a trav
´
es
de Modbus/TCP a una Raspberry Pi 4B que convierte este
protocolo a MQTT/TLS para dar seguridad a la transmisi
´
on
de los datos, ya que el servidor con el dashboard se encuentra
fuera de la red de campo. El an
´
alisis de performance del
sistema h
´
ıbrido e
´
olico-solar de baja potencia es posible
debido a la disponibilidad y persistencia de los datos en
el servidor remoto y localmente en la tarjeta CF del datalogger.
Palabras clave : sistema de monitoreo, protocolo MQTT/TLS,
protocolo Modbus, energ
´
ıa renovable
Abstract— This work presents a renewable energy
measurement system with two Modbus protocol connections
(RTU/Serial to internal modules, TCP to external units) and
achieves a TLS-encrypted link between the datalogger module
and a centralized remote dashboard application. Recent
installation and commissioning of high quality instruments
allow for reliable information to be collected, and the system
offers remote monitoring and data persistence. The logger
acquires wind data using Thies sensors installed on the wind
turbine tower, and current and voltage from both the wind
turbine and an array of photovoltaic panels. Energy is stored
in a battery bank and is used to supply electric power to a
greenhouse. In this nearby building, an additional module
to measure temperature and humidity of the plant-growing
environment was developed and programmed. The module
communicates via RS485 using Modbus RTU with the main
datalogger, which also uses an internal network connection
through Modbus TCP to a Raspberry Pi4B board. The Pi
board converts the readings to MQTT/TLS, an added security
feature before sending data to the remote server which runs
the dashboard application. A continuous performance analysis
of the renewable energy unit is possible due to the availability
and persistence of real-time data on the server and also on
the CF card of the datalogger.
Keywords: Monitoring system, Modbus protocol, MQTT/TLS
protocol, renewable energy
I. INTRODUCCI
´
ON
El uso de sistemas de registro basados en dataloggers de
tipo industrial ha sido una necesidad desde las primeras
instalaciones h
´
ıbridas de energ
´
ıa renovable, por ejemplo
[1] en sistemas remotos de comunicaciones que requieren
una elevada confiabilidad de datos. Algunos de los equipos
programables de mayor prestigio tienen una larga trayectoria
en el sector [2], lo cual los convierte en sistemas de
referencia. La difusi
´
on creciente del acceso a Internet en
ambientes rurales ha incentivado el inter
´
es por emplear
sistemas de registro que incorporen conectividad estable,
que la misma cumpla con los requerimientos b
´
asicos de
ciberseguridad, sumando a todo esto la persistencia de datos.
Si bien existen alternativas comerciales que implementan
este tipo de sistemas (ej. Schneider Insight - Conext /
Xanbus [3]) en general su dise
˜
no es cerrado y utilizan
protocolos propietarios.
El presente trabajo describe internamente un sistema
de este tipo denominado SISMED/RG24 que es utilizado
para el monitoreo de un sistema e
´
olico-fotovoltaico de uso
didactico [7] instalado en el Campus de la Universidad
Nacional de la Patagonia Austral. El sistema en su conjunto,
Revista elektron, Vol. 6, No. 2, pp. 120-128 (2022)
Recibido: 20/03/22; Aceptado: 23/08/22
Creative Commons License - Attribution-NonCommercial-
NoDerivatives 4.0 International (CC BY-NC-ND 4.0)
https://doi.org/10.37537/rev.elektron.6.2.160.2022
Original Article